Schneider Electric Zelio Logic Discrete I/O extension module 6 I/O 100-240V AC for Zelio Logic SR3XT61FU
AED 211.05
(Price Includes VAT)
Order Now & Get it by 2 days
Sold by: Marketplace
Cash on
Delivery
7 Days
Returnable
15+
Years Of Trust
15+
Branches
Brand : Schneider Electric
Type : Discrete I/O Extension Module
Collections
Description
Schneider Electric SR3XT61FU Zelio Logic Discrete Input Or Output Extension Module uses a supply voltage of 100V-240VAC. It has 6 input/output contacts with screw terminals. It allows for simple ladder programming that is also suitable for non-professionals.
Features
- Supply voltage of 100V-240VAC
- It has 6 input/output contacts with screw terminals.
Brand | Schneider Electric |
Item Name | Discrete I/O Extension Module |
Model | SR3XT61FU |
Connections - Terminals | Screw terminals, 1 x 0.25...1 x 2.5 mm² (AWG 24...AWG 14) flexible with cable end, screw terminals, 2 x 0.25...2 x 0.75 mm² (AWG 24...AWG 18) flexible with cable end, screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 25...AWG 14) semi-solid, screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 25...AWG 14) solid, screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) solid |
IP Degree Of Protection | IP20 (terminal block) conforming to IEC 60529, IP40 (front panel) conforming to IEC 60529 |
Mechanical Durability | 10000000 cycles for relay output |
Supply Voltage Limits | 85-264 V |
Tightening Torque | 0.5 N.m |
Contacts Type And Composition | NO for relay output |
Supply Frequency | 50/60 Hz |
Number Or Control Scheme Lines | 120-120 with ladder programming |
Clock Drift | 12 min/year at 0-55 °C |
Discrete Input Current | 0.6 mA |
Current State 1 Guaranteed | >= 0.17 mA (discrete input) |
Voltage State 1 Guaranteed | >= 79 V for discrete input |
Switching Capacity in mA | >= 10 mA at 12 V (relay output) |
Maximum Altitude Transport | 3048 m |
Cycle Time | 6-90 ms |
Discrete Input Frequency | 57...63 Hz, 47...53 Hz |
Checks | Program Memory on each power up |
Disturbance Radiated/Conducted | Class B conforming to EN 55022-11 group 1 |
Output Thermal Current | 8 A for all 2 outputs for relay output |
Backup Time | 10 years at 25 °C |
Discrete Input Voltage | 100...240 V AC |
Voltage State 0 Guaranteed | <= 40 V for discrete input |
Operating Rate in Hz | 0.1 Hz (at Ie) for relay output, 10 Hz (no load) for relay output |
Current State 0 Guaranteed | <= 0.5 mA (discrete input) |
Reverse Polarity Protection | With |
Discrete Input Number | 4 |
Ambient Air Temperature For Operation | -20-40 °C in non-ventilated enclosure conforming to IEC 60068-2-1 and IEC 60068-2-2, -20-55 °C conforming to IEC 60068-2-1 and IEC 60068-2-2 |
Standards | EN/IEC 61000-4-11, EN/IEC 60068-2-27 Ea, EN/IEC 61000-4-4 level 3, EN/IEC 61000-4-5, EN/IEC 61000-4-12, EN/IEC 60068-2-6 Fc, EN/IEC 61000-4-2 level 3, EN/IEC 61000-4-3, EN/IEC 61000-4-6 level 3 |
Environmental Characteristic | EMC directive conforming to EN/IEC 61000-6-2, EMC directive conforming to EN/IEC 61000-6-3, EMC directive conforming to EN/IEC 61000-6-4, EMC directive conforming to EN/IEC 61131-2 zone B, low voltage directive conforming to EN/IEC 61131-2 |
Ambient Air Temperature For Storage | -40-70 °C |
Input Impedance | 350 kOhm for discrete input |
Electrical Durability | AC-15: 500000 cycles at 230 V, 0.9 A for relay output conforming to EN/IEC 60947-5-1, AC-12: 500000 cycles at 230 V, 1.5 A for relay output conforming to EN/IEC 60947-5-1, DC-13: 500000 cycles at 24 V, 0.6 A for relay output conforming to EN/IEC 60947-5-1, DC-12: 500000 cycles at 24 V, 1.5 A for relay output conforming to EN/IEC 60947-5-1 |
Weight | 0.125 kg |