Schneider Electric Zelio Logic Discrete I/O Extension Module 14 I/O 24V DC SR3XT141BD

AED 421.05

(Price Includes VAT)

Delivery truck icon

Order Now & Get it by 2 days

Shop logo

Sold by: Marketplace

Free delivery inside Dubai on all orders with no order limit. Pay in 4 interest-free installments for Dubai orders using Tabby.
Cash on delivery payment method icon
Cash on Delivery
7 Days Returnable icon
7 Days Returnable
15+ Years Of Trust icon
15+ Years Of Trust
15+ Branches icon
15+ Branches
Quantity

Brand : Schneider Electric

Type : Discrete I/O Extension Module

Collections

Description

Schneider Electric SR3XT141BD Zelio Logic Discrete Input Or Output Extension Module uses a supply voltage of 24V DC. It has 14 input/output contacts with screw terminals. It allows for simple ladder programming that is also suitable for non-professionals.

Features
  • It features 14 I/Os and 120 control lines with ladder programming.
  • IP20 protection 
  • A nominal supply voltage of 24 V DC 
Specifications
Brand Schneider Electric
Item Name Discrete I/O Extension Module
Model SR3XT141BD
Rated Impulse Withstand Voltage 4 kV conforming to EN/IEC 60947-1 and EN/IEC 60664-1
Rated Supply Voltage 24 V DC
Connections - Terminals Screw terminals, 1 x 0.25...1 x 2.5 mm² (AWG 24...AWG 14) flexible with cable end, screw terminals, 2 x 0.25...2 x 0.75 mm² (AWG 24...AWG 18) flexible with cable end, screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 25...AWG 14) semi-solid, screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 25...AWG 14) solid, screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) solid
IP Degree Of Protection IP20 (terminal block) conforming to IEC 60529, IP40 (front panel) conforming to IEC 60529
Mechanical Durability 10000000 cycles for relay output
Operating Altitude 2000 m
Output Voltage Limits 24...250 V AC (relay output), 5...30 V DC (relay output)
Overvoltage Category III Conforming to EN/IEC 60664-1
Pollution Degree 2 Conforming to EN/IEC 61131-2
Certifications GL, C-Tick, GOST, UL, CSA
Range Of Product Zelio Logic
Relative Humidity 95-95 % without condensation or dripping water
Supply Voltage Limits 19.2-30 V
tightening torque 0.5 N.m
Contacts Type And Composition NO for relay output
Number Or Control Scheme Lines 120-120 with ladder programming
Clock Drift 12 min/year at 0-55 °C
Discrete Input Current 4 mA
Current State 1 Guaranteed >= 1.2 mA (IB...IG used as discrete input circuit), >= 2.2 mA (I1...IA and IH...IR discrete input circuit)
Voltage State 1 Guaranteed >= 15 V for I1...IA and IH...IR discrete input circuit, >= 15 V for IB...IG used as discrete input circuit
Switching Capacity in mA >= 10 mA at 12 V (relay output)
Maximum Altitude Transport 3048 m
Cycle Time 6-90 ms
Checks Program Memory on each power up
Disturbance Radiated/Conducted Class B conforming to EN 55022-11 group 1
Output Thermal Current 5 A for 2 outputs for relay output, 8 A for 4 outputs for relay output
Backup Time 10 years at 25 °C
Discrete Input Voltage 24 V DC
Voltage State 0 Guaranteed <= 5 V for I1...IA and IH...IR discrete input circuit, <= 5 V for IB...IG used as discrete input circuit
Operating Rate in Hz 0.1 Hz (at Ie) for relay output, 10 Hz (no load) for relay output
Input Compatibility 3-wire proximity sensors PNP for discrete input
Discrete Input Type Resistive
Current State 0 Guaranteed <= 0.5 mA (IB...IG used as discrete input circuit), <= 0.75 mA (I1...IA and IH...IR discrete input circuit)
Reverse Polarity Protection With
Discrete Input Number 8 conforming to EN/IEC 61131-2 type 1
Voltage Range 19...30 V
Counting Frequency 1 kHz for discrete input
Ambient Air Temperature For Operation -20-40 °C in non-ventilated enclosure conforming to IEC 60068-2-1 and IEC 60068-2-2, -20-55 °C conforming to IEC 60068-2-1 and IEC 60068-2-2
Standards EN/IEC 61000-4-6 level 3, EN/IEC 61000-4-3, EN/IEC 61000-4-4 level 3, EN/IEC 61000-4-5, EN/IEC 61000-4-12, EN/IEC 61000-4-11, EN/IEC 60068-2-6 Fc, EN/IEC 61000-4-2 level 3, EN/IEC 60068-2-27 Ea
Environmental Characteristic EMC directive conforming to EN/IEC 61000-6-2, EMC directive conforming to EN/IEC 61000-6-3, EMC directive conforming to EN/IEC 61000-6-4, EMC directive conforming to EN/IEC 61131-2 zone B, low voltage directive conforming to EN/IEC 61131-2
Ambient Air Temperature For Storage -40-70 °C
Input Impedance 12 kOhm for IB...IG used as discrete input circuit, 7.4 kOhm for I1...IA and IH...IR discrete input circuit
Electrical Durability AC-15: 500000 cycles at 230 V, 0.9 A for relay output conforming to EN/IEC 60947-5-1, AC-12: 500000 cycles at 230 V, 1.5 A for relay output conforming to EN/IEC 60947-5-1, DC-13: 500000 cycles at 24 V, 0.6 A for relay output conforming to EN/IEC 60947-5-1, DC-12: 500000 cycles at 24 V, 1.5 A for relay output conforming to EN/IEC 60947-5-1
Weight 0.22 kg
WhatsApp Contact Button - Click to chat on WhatsApp