Brand : Schneider Electric
Item Name : Control Relay
Model : CA2KN40P7
Conventional Free Air Thermal Current : 10 A (at 50 °C)
Control Circuit Voltage : 230V AC 50/60 Hz
Rated Insulation Voltage : 690 V conforming to IEC 60947, 750 V conforming to VDE 0110 group C, 690 V conforming to BS 5424, 600 V conforming to CSA C22.2 No 14
Ambient Air Temperature For Storage : -50-80 °C
Associated Fuse Rating : 10 A gG conforming to IEC 60947, 10 A gG conforming to VDE 0660
Compatibility Code : CA2K
Connections - Terminals : Screw Clamp Terminals 1 cable(s) 1.5-4 mm²solid, screw clamp terminals 2 cable(s) 1.5-4 mm²solid, screw clamp terminals 1 cable(s) 0.75-4 mm²flexible with cable end, screw clamp terminals 2 cable(s) 0.75-4 mm²flexible without cable end, screw clamp terminals 1 cable(s) 0.34-1.5 mm²flexible with cable end, screw clamp terminals 2 cable(s) 0.34-1.5 mm²flexible without cable end
Contactor Application : Control Circuit
Control Circuit Type : AC at 50/60 Hz
Control Circuit Voltage Limits : Drop-out: 0.2...0.75 Uc (at <50 °C), operational: 0.8...1.15 Uc (at <50 °C)
Depth : 57 mm
Flame Retardance : V1 conforming to UL 94, requirement 2 conforming to NF F 16-101, requirement 2 conforming to NF F 16-102
Height : 58 mm
Heat Dissipation : 1.3-1.3 W
Hold-in Power Consumption in VA : 4.5-4.5 VA (at 20 °C)
Inrush Power in VA : 30-30 VA (at 20 °C)
IP Degree Of Protection : IP2X
Irms Rated Making Capacity : 110 A conforming to IEC 60947
Maximum Operating Rate : 10000 cyc/h
Mechanical Durability : 10 Mcycles
Mechanical Robustness : vibrations contactor open: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6, vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6, shocks contactor open: 10 Gn for 11 ms conforming to IEC 60068-2-27, shocks contactor closed: 15 Gn for 11 ms conforming to IEC 60068-2-27
Minimum Switching Current : 5 mA
Minimum Switching Voltage : 17 V
Mounting Support : Rail, Plate
Non-overlap Time : 1.5 ms on energisation between NC and NO contact, 1.5 ms on de-energisation between NC and NO contact
Operating Altitude : 2000 m without derating
Operating Time : 10...20 ms coil de-energisation and NO opening, 10...20 ms coil energisation and NO closing
Pole Contact Composition : 4NO
Certifications : CB Scheme, CCC, UL, CSA, EAC, CE, UKCA
Protective Treatment : TC conforming to IEC 60068
Range Of Product : TeSys K Control Relay
Rated Operational Voltage Limits : <= 690 V <= 400 Hz
Tightening Torque : 1.3 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm, 1.3 N.m - on screw clamp terminals - with screwdriver Philips No 26 mm, 1.3 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
Utilisation Category : DC-13, AC-15
Width : 45 mm
Immunity to Microbreaks : 2 ms
Non Overlap Distance : 0.5 mm
Ambient Air Temperature For Operation : -25-50 °C
Insulation Resistance : > 10 MOhm
Standards : EN/IEC 60947-4-1, GB/T 14048.4, UL 60947-4-1, CSA C22.2 No 60947-4-1, JIS C8201-4-1
Weight : 0.18 kg