Schneider Electric TeSys K Auxiliary Contact Block 4 NC Screw Clamps Terminals LA1KN04
(Price Includes VAT)
Due to current global supply and market conditions, product prices may occasionally change. If there is any change in the price of items in your order, our customer support team will reach out to you for confirmation before proceeding further. We sincerely appreciate your understanding and thank you for your continued support.
Order Now & Get it by 2 - 3 Working Days
Sold by: Marketplace
Brand : Schneider Electric
Type : Auxiliary Contact Block
Description
Schneider Electric LA1KN04 TeSys K Auxiliary Contact Block for LC.K, LP.K, CA.K contactors with screw terminals (except LP4K, LP5K, CA4K). Offers 4 normally closed contacts rated up to 10A, 690VAC, and connection via screw terminal blocks. Front clip mounting ensures high reliability and durability. Multi-standard certification (IEC, UL, CSA, CCC), Green Premium compliant (RoHS/REACh).
Features
- Front mounting with Screw clamp terminals
- Instantaneous auxiliary contacts operation
- Conventional Free Air Thermal Current 10 A
- Minimum switching current of 5mA at 17V
| Brand | Schneider Electric |
| Item Name | Auxiliary Contact Block |
| Model | LA1KN04 |
| Conventional Free Air Thermal Current | 10 A (at 60 °C) |
| Rated Insulation Voltage | 690 V conforming to IEC 60947-5-1, 600 V conforming to UL 60947-5-1, 600 V conforming to CSA C22.2 No 60947-5-1 |
| Ambient Air Temperature For Storage | -50-80 °C |
| Connections - Terminals | Screw clamp terminals 1 cable(s) 0.34-1.5 mm²flexible with cable end, screw clamp terminals 1 cable(s) 0.75-4 mm²flexible without cable end, screw clamp terminals 1 cable(s) 1.5-4 mm²rigid, screw clamp terminals 2 cable(s) 0.34-1.5 mm²flexible with cable end, screw clamp terminals 2 cable(s) 0.75-4 mm²flexible without cable end, screw clamp terminals 2 cable(s) 1.5-4 mm²rigid |
| Compatibility Code | LA1 |
| Depth | 35 mm |
| Height | 30 mm |
| IP Degree Of Protection | IP20 conforming to IEC 60529 |
| Irms Rated Making Capacity | 110 A at <= 690 V AC conforming to IEC 60947 |
| Minimum Switching Current | 5 mA |
| Minimum Switching Voltage | 17 V |
| Operating Altitude | 2000 m |
| Pole Contact Composition | 4 NC |
| Certifications | CB Scheme, CCC, UL, CSA, CE, UKCA |
| Protective Treatment | TC conforming to IEC 60068 |
| Range Of Product | TeSys K, TeSys K control relay |
| Rated Operational Voltage Limits | 690 V AC 25...400 Hz |
| Tightening Torque | 1.3 N.m - with screwdriver Philips No 2, 1.3 N.m - with screwdriver pozidriv No 2 |
| Width | 38 mm |
| Permissible Short-time Rating | 80 A 1 s, 60 A 500 ms, 110 A 100 ms |
| Auxiliary Contacts Operation | Instantaneous |
| Shielding Continuity Terminal | Without |
| Ambient Air Temperature For Operation | -25-50 °C |
| Standards | EN/IEC 60947-5-1, UL 60947-5-1, CSA C22.2 No 60947-5-1, GB/T 14048.5, JIS C8201-5-1 |
| Environmental Characteristic | Normal Environment |
| Insulation Resistance | > 10 MOhm |
| Mounting Location | Front |
| Range Compatibility | TeSys K LC1K, TeSys K CA2K, TeSys K CA3K |
| Weight | 0.045 kg |