Schneider Electric TeSys D contactor 3P(3 NO) AC-3 <= 440V 150A 220V AC 50/60Hz Coil LC1D150M7
(Price Includes VAT)
Order Now & Get it by 2 days
Sold by: Marketplace
Brand : Schneider Electric
Type : Contactor
Description
Schneider Electric LC1D150M7 TeSys D Contactor is an electrical device used to control the flow of electricity in a circuit. It is commonly used in control circuits to start and stop motors, and for other applications where heavy-duty switching is required. The contactor is designed for three-phase systems. It means it can handle three separate conductors for power distribution. AC-3 is specifically for starting and stopping squirrel cage motors.
The contactor is rated operational voltage (440V) and the maximum current it can handle under normal operating conditions (150A). This means the contactor is suitable for systems with a voltage of up to 440V and a current of up to 150A. 220V AC 50/60 Hz Coil is the control voltage for the contactor. The coil is what electromagnetically closes the contacts in the contactor. The coil operates on a 220V AC supply and is compatible with both 50Hz and 60Hz frequencies.
So, in summary, Schneider Electric LC1D150M7 TeSys D Contactor is designed for heavy-duty use in three-phase systems with voltages up to 440V and currents up to 150A. It's controlled by a 220V AC coil that can operate on either 50Hz or 60Hz frequencies. This type of contactor is commonly used in industrial applications for controlling motors and other high-power equipment.
Features
- 150A TP AC3 Contactor AC3 220V AC Coil
- Control the flow of electric current in a circuit
- 3-pole contactor for connection by screw clamp terminals
Brand | Schneider Electric |
Item Name | Contactor |
Model | LC1D150M7 |
Conventional Free Air Thermal Current | 200 A (at 60 °C) for power circuit |
Control Circuit Voltage | 220 V AC 50/60 Hz |
Rated Insulation Voltage | Power Circuit: 690 V conforming to IEC 60947-4-1, power circuit: 600 V CSA certified, power circuit: 600 V UL certified, signalling circuit: 690 V conforming to IEC 60947-1, signalling circuit: 600 V CSA certified, signalling circuit: 600 V UL certified |
Rated Impulse Withstand Voltage | 8 kV conforming to IEC 60947 |
Associated Fuse Rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1, 315 A gG at <= 690 V coordination type 1 for power circuit, 250 A gG at <= 690 V coordination type 2 for power circuit |
Auxiliary Contact Composition | 1 NO + 1 NC |
Auxiliary Contacts Type | Type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1, type mirror contact 1 NC conforming to IEC 60947-4-1 |
Average Impedance | 0.6 mOhm - Ith 200 A 50 Hz for power circuit |
Climatic Withstand | Conforming to IACS E10 exposure to damp heat, conforming to IEC 60947-1 Annex Q category D exposure to damp heat |
Coil Technology | built-in bidirectional peak limiting diode suppressor |
Compatibility Code | LC1D |
Connections - Terminals | control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end, control circuit: screw clamp terminals 1 1-2.5 mm² - cable stiffness: flexible with cable end, control circuit: screw clamp terminals 1 1-2.5 mm² - cable stiffness: flexible without cable end, control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible without cable end, control circuit: screw clamp terminals 1 1-2.5 mm² - cable stiffness: solid without cable end, control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: solid without cable end, power circuit: connector 1 10-120 mm² - cable stiffness: flexible without cable end, power circuit: connector 2 10-50 mm² - cable stiffness: flexible without cable end, power circuit: connector 1 10-120 mm² - cable stiffness: flexible with cable end, power circuit: connector 2 10-50 mm² - cable stiffness: flexible with cable end, power circuit: connector 1 10-120 mm² - cable stiffness: solid without cable end, power circuit: connector 2 10-50 mm² - cable stiffness: solid without cable end |
Contact Compatibility | M13 |
Contactor Application | Motor Control, Resistive Load |
Control Circuit | Type AC at 50/60 Hz |
Control Circuit Voltage Limits | 0.3...0.5 Uc (-40-70 °C):drop-out AC 50/60 Hz, 0.8...1.15 Uc (-40-55 °C):operational AC 50/60 Hz, 1...1.15 Uc (55-70 °C):operational AC 50/60 Hz |
Depth | 136 mm |
Electrical Durability | 0.85 Mcycles 150 A AC-3 at Ue <= 440 V, 1 Mcycles 200 A AC-1 at Ue <= 440 V, 0.85 Mcycles 150 A AC-3e at Ue <= 440 V |
Fire Resistance | 850 °C Conforming to IEC 60695-2-1 |
Flame Retardance | V1 Conforming to UL 94 |
Heat Dissipation | 3-4.5 W at 50/60 Hz |
Height | 158 mm |
Hold-in Power Consumption in VA | 2-18 VA 60 Hz cos phi 0.9 (at 20 °C), 2-18 VA 50 Hz cos phi 0.9 (at 20 °C) |
Inrush Power in VA | 280-350 VA 60 Hz cos phi 0.9 (at 20 °C), 280-350 VA 50 Hz cos phi 0.9 (at 20 °C) |
Insulation Resistance | > 10 MOhm for Signalling Circuit |
IP Degree Of Protection | IP20 front face conforming to IEC 60529 |
Irms Rated Making Capacity | 140 A AC for signalling circuit conforming to IEC 60947-5-1, 250 A DC for signalling circuit conforming to IEC 60947-5-1, 1660 A at 440 V for power circuit conforming to IEC 60947 |
Maximum Operating Rate | 1200 cyc/h 60 °C |
Mechanical Durability | 8 Mcycles |
Mechanical Robustness | vibrations contactor open (2 Gn, 5...300 Hz) , vibrations contactor closed (4 Gn, 5...300 Hz) , shocks contactor closed (15 Gn for 11 ms) , shocks contactor open (6 Gn for 11 ms) |
Minimum Switching Current | 5 mA for signalling circuit |
Minimum Switching Voltage | 17 V for signalling circuit |
Motor Power hp | 40 hp at 200/208 V AC 50/60 Hz for 3 phases motors, 50 hp at 230/240 V AC 50/60 Hz for 3 phases motors, 100 hp at 460/480 V AC 50/60 Hz for 3 phases motors, 125 hp at 575/600 V AC 50/60 Hz for 3 phases motors |
Motor Power kW | 40 kW at 220...230 V AC 50/60 Hz (AC-3), 75 kW at 380...400 V AC 50/60 Hz (AC-3), 80 kW at 415...440 V AC 50/60 Hz (AC-3), 90 kW at 500 V AC 50/60 Hz (AC-3), 100 kW at 660...690 V AC 50/60 Hz (AC-3), 75 kW at 1000 V AC 50/60 Hz (AC-3), 22 kW at 400 V AC 50/60 Hz (AC-4), 40 kW at 220...230 V AC 50/60 Hz (AC-3e), 75 kW at 380...400 V AC 50/60 Hz (AC-3e), 80 kW at 415...440 V AC 50/60 Hz (AC-3e), 90 kW at 500 V AC 50/60 Hz (AC-3e), 100 kW at 660...690 V AC 50/60 Hz (AC-3e), 75 kW at 1000 V AC 50/60 Hz (AC-3e) |
Mounting Support | Rail, plate |
Non-overlap Time | 1.5 ms on de-energisation between NC and NO contact, 1.5 ms on energisation between NC and NO contact |
Operating Altitude | 0...3000 m |
Operating Time | 20...35 ms closing, 40...75 ms opening |
Overvoltage Category | III |
Permissible Ambient Air Temperature Around The Device | -40-60 °C, 60-70 °C with derating |
Pole Contact Composition | 3 NO |
Poles Description | 3P |
Pollution Degree | 3 |
Power Dissipation Per Pole | 24 W AC-1, 13.5 W AC-3, 13.5 W AC-3e |
Certifications | CCC, LROS (Lloyds register of shipping), GL, GOST, RINA, CSA, BV, UL, DNV, UKCA, CE |
Protective Cover | With |
Protective Treatment | TH Conforming to IEC 60068-2-30 |
Range | TeSys, TeSys Deca |
Rated Breaking Capacity | 1400 A at 440 V for power circuit conforming to IEC 60947 |
Rated Operational Voltage Limits | power circuit: <= 1000 V AC 25...400 Hz, power circuit: <= 300 V DC |
Safety Reliability Level | B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1, B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
Signalling Circuit Frequency | 25...400 Hz |
Standards | CSA C22.2 No 14, EN 60947-4-1, EN 60947-5-1, IEC 60947-4-1, IEC 60947-5-1, UL 508 |
Tightening Torque | control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm, control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver Philips No 2, power circuit: 12 N.m - on connector hexagonal screw head 4 mm, control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver pozidriv No 2 |
Utilisation Category | AC-3, AC-1, AC-4, AC-3e |
Width | 55 mm |
Rated Short-time Withstand Current | 250 A 40 °C - 10 min for power circuit, 580 A 40 °C - 1 min for power circuit, 1200 A 40 °C - 10 s for power circuit, 1400 A 40 °C - 1 s for power circuit, 100 A - 1 s for signalling circuit, 120 A - 500 ms for signalling circuit, 140 A - 100 ms for signalling circuit |
Weight | 2.5 kg |