Schneider Electric TeSys D Auxiliary Contact Block 1NO Front Mounting Screw Clamp Terminals LADN10
(Price Includes VAT)
Order Now & Get it by 2 days
Sold by: Marketplace
Brand : Schneider Electric
Type : Auxiliary Contact Block
Description
Schneider Electric LADN10 TeSys D Auxiliary Contact Block is an electrical component used in conjunction with a main contactor or relay. It provides additional contacts that can be used to control or monitor other electrical devices in a circuit.
NO means that the contact is open when the relay or contactor coil is not energized. When the coil is energized, the contact closes. Screw Clamp Terminal is the point on the contact block where wires can be connected. Screw clamp terminals use screws to secure the wires in place, providing a secure and reliable connection.
So, Schneider Electric LADN10 TeSys D Auxiliary Contact Block is a component with one normally open contact, designed to be mounted on the front surface of a panel or enclosure, and it uses screw clamp terminals for wire connections. This component is often used in control circuits to provide an additional set of contacts for controlling other devices.
Features
- Front mounting with Screw clamp terminals
- Instantaneous auxiliary contacts operation
- Conventional Free Air Thermal Current 10 A
- Minimum switching current of 5mA at 17V
- Mechanical durability 30 million cycles
Brand | Schneider Electric |
Item Name | Auxiliary Contact Block |
Model | LADN10 |
Color | Dark Grey |
Conventional Free Air Thermal Current | 10 A (at 60 °C) |
Rated Insulation Voltage | 690 V conforming to IEC 60947-5-1, 600 V conforming to UL, 600 V conforming to CSA |
Ambient Air Temperature For Storage | -60-80 °C |
Connections - Terminals | screw clamp terminals 1 cable(s) 1-4 mm²flexible with cable end, screw clamp terminals 1 cable(s) 1-4 mm²flexible without cable end, screw clamp terminals 2 cable(s) 1-2.5 mm²flexible with cable end, screw clamp terminals 2 cable(s) 1-4 mm²flexible without cable end, screw clamp terminals 1 cable(s) 1-4 mm²rigid without cable end, screw clamp terminals 2 cable(s) 1-4 mm²rigid without cable end |
Depth | 35 mm |
Height | 48 mm |
IP Degree Of Protection | IP20 conforming to IEC 60529 |
Irms Rated Making Capacity | 140 A AC conforming to IEC 60947-5-1, 250 A DC conforming to IEC 60947-5-1 |
Mechanical Durability | 30 Mcycles |
Minimum Switching Current | 5 mA |
Minimum Switching Voltage | 17 V |
Non-overlap Time | 1.5 ms on de-energisation no overlap between NC and NO contact, 1.5 ms on energisation no overlap between NC and NO contact |
Operating Altitude | 3000 m |
Pole Contact Composition | 1NO |
Certifications | CB, UL, CSA, CCC, EAC, UKCA |
Protective Treatment | TH Conforming to IEC 60068 |
Range | TeSys, TeSys Deca |
Rated Operational Voltage Limits | 690 V AC 25...400 Hz |
Tightening Torque | 1.7 N.m - with screwdriver flat Ø 6 mm, 1.7 N.m - with screwdriver Philips No 2, 1.7 N.m - with screwdriver pozidriv No 2 |
Width | 13 mm |
Permissible Short-time Rating | 100 A 60 °C 1 s, 120 A 60 °C 500 ms, 140 A 60 °C 100 ms |
Auxiliary Contacts Operation | Instantaneous |
Shielding Continuity Terminal | Without |
Ambient Air Temperature For Operation | -5-60 °C |
Standards | EN/IEC 60947-5-1, UL 60947-5-1, CSA C22.2 No 60947-5-1, GB/T 14048.5 |
Rated Operational Current | 6 A at 120 V AC-15, 1.04 A at 690 V AC-15, 0.55 A at 125 V DC-13, 0.1 A at 600 V DC-13 |
Environmental Characteristic | Normal Environment |
Insulation Resistance | > 10 MOhm |
Mounting Location | Front |
Range Compatibility | TeSys Deca LC1D80/95 3P, TeSys Deca LC1D80 4P, TeSys Deca LC1D40008, TeSys Deca LC1D65008, TeSys F LC1F, TeSys Deca LC1D115 |
Weight | 0.02 kg |