Brand : Schneider Electric
Item Name : Analog Input Module
Model : TM3TI4
Resistance To Electrostatic Discharge : 8 kV in air conforming to EN/IEC 61000-4-2, 4 kV on contact conforming to EN/IEC 61000-4-2
Rated Supply Voltage : 24 V DC
Current Consumption : 45 mA at 5 V DC via bus connector, 50 mA at 5 V DC via bus connector, 35 mA at 24 V DC via external supply, 40 mA at 24 V DC via external supply
Depth : 70 mm
Height : 90 mm
IP Degree Of Protection : IP20
Marking : CE
Mounting Support : Top hat type TH35-15 rail conforming to IEC 60715, top hat type TH35-7.5 rail conforming to IEC 60715, plate or panel with fixing kit
Operating Altitude : 0...2000 m
Pollution Degree : 2
Range Of Product : Modicon TM3
Relative Humidity : 10-95 %, without condensation (in operation), 10-95 %, without condensation (in storage)
Shock Resistance : 15 gn for 11 ms
Supply Voltage Limits : 20.4-28.8 V
Width : 23.6 mm
Immunity To Microbreaks : 10 ms
Resistance To Electromagnetic Fields : 10 V/m 80 MHz...1 GHz conforming to EN/IEC 61000-4-3, 3 V/m 1.4 GHz...2 GHz conforming to EN/IEC 61000-4-3, 1 V/m 2 GHz...3 GHz conforming to EN/IEC 61000-4-3
Surge Withstand : 1 kV power supply common mode conforming to EN/IEC 61000-4-5, 0.5 kV power supply differential mode conforming to EN/IEC 61000-4-5, 1 kV input common mode conforming to EN/IEC 61000-4-5
Resistance To Fast Transients : 1 kV (I/O) conforming to EN/IEC 61000-4-4
Electromagnetic Emission : Radiated emissions - test level: 40 dBμV/m QP class A ( 10 m) at 30-230 MHz conforming to EN/IEC 55011, radiated emissions - test level: 47 dBμV/m QP class A ( 10 m) at 230-1000 MHz conforming to EN/IEC 55011
Temperature Drift : +/- 0.01 %FS/°C
Analogue Input Resolution : 16 bits, 15 bits + sign
Analogue Input Number : 4
Analogue Input Type : Current 4...20 mA, current 0...20 mA, voltage 0...10 V, voltage - 10...10 V, thermocouple - 200...1000 °C with thermocouple J, thermocouple - 200...1300 °C with thermocouple K, thermocouple 0...1760 °C with thermocouple R, thermocouple 0...1760 °C with thermocouple S, thermocouple 0...1820 °C with thermocouple B, thermocouple - 200...400 °C with thermocouple T, thermocouple - 200...1300 °C with thermocouple N, thermocouple - 200...800 °C with thermocouple E, thermocouple 0...2315 °C with thermocouple C, Ni 100/Ni 1000 temperature probe - 60...180 °C, Pt 100 temperature probe - 200...850 °C, Pt 1000 temperature probe - 200...600 °C
Repeat Accuracy : +/-0.5 %FS
LSB Value : 2.44 mV 0...10 Vvoltage, 4.88 mV - 10...10 Vvoltage, 4.88 µA 0...20 mAcurrent, 3.91 µA 4...20 mAcurrent, 0.1 °Ctemperature probe, 0.1 °Cthermocouple
Conversion Time : 100 ms + 100 ms per channel + 1 controller cycle time for analogue input thermocouple, 100 ms + 100 ms per channel + 1 controller cycle time for analogue input temperature probe, 10 ms + 10 ms per channel + 1 controller cycle time for analogue input voltage/current
Resistance To Conducted Disturbances : 10 V 0.15...80 MHz conforming to EN/IEC 61000-4-6, 3 V spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) conforming to Marine specification (LR, ABS, DNV, GL)
Non-Linearity : +/- 0.2 %FS
Absolute Accuracy Error : +/- 0.2 % of full scale at 25 °C for analogue input voltage/current, +/- 0.2 % of full scale at 25 °C for Pt 100/Pt 1000, Ni 100/ Ni 1000 temperature probe, +/- 0.2 % of full scale at 25 °C for thermocouple C 0...2315 °C, +/- 6 °C at 25 °C for thermocouple R, S 0...200 °C, +/- 0.2 % of full scale at 25 °C for thermocouple R, S 200...1760 °C, +/- 0.2 % of full scale at 25 °C for thermocouple B 300...1820 °C, +/- 0.4 % of full scale at 25 °C for thermocouple K - 200...0 °C, +/- 0.2 % of full scale at 25 °C for thermocouple K 0...1300 °C, +/- 0.4 % of full scale at 25 °C for thermocouple J - 200...0 °C, +/- 0.2 % of full scale at 25 °C for thermocouple J 0...1000 °C, +/- 0.4 % of full scale at 25 °C for thermocouple E - 200...0 °C, +/- 0.2 % of full scale at 25 °C for thermocouple E 0...800 °C, +/- 0.4 % of full scale at 25 °C for thermocouple T - 200...0 °C, +/- 0.2 % of full scale at 25 °C for thermocouple T 0...400 °C, +/- 0.4 % of full scale at 25 °C for thermocouple N - 200...0 °C, +/- 0.2 % of full scale at 25 °C for thermocouple N 0...1300 °C
Cross Talk : <= 1 LSB
Resistance to Magnetic Fields : 30 A/m conforming to EN/IEC 61000-4-8
Sampling Duration : 10 ms, analogue input type: voltage/current, 100 ms, analogue input type: voltage/current, 100 ms, analogue input type: thermocouple, 100 ms, analogue input type: temperature probe
Permissible Continuous Overload : 13 V, analogue input type: voltage, 40 mA, analogue input type: current
Vibration Resistance : 3.5 mm at 5-8.4 Hz on DIN rail, 3 gn at 8.4-150 Hz on DIN rail
Ambient Air Temperature For Operation : -10-55 °C horizontal installation, -10-35 °C vertical installation
Standards : EN/IEC 61010-2-201, EN/IEC 61131-2
Local Signalling : 1 LED (green) for PWR
Electrical Connection : 10 x 1.5 mm² removable screw terminal block with pitch 3.81 mm adjustment for inputs and supply, 10 x 1.5 mm² removable screw terminal block with pitch 3.81 mm adjustment for inputs
Input Impedance : <= 50 Ohm current, >= 1 MOhm voltage, >= 1 MOhm thermocouple, >= 1 MOhm temperature probe
Storage Altitude : 0-3000 m
Insulation : Between input and supply at 1500 V AC, between input and internal logic at 500 V AC
Load Type : Resistive
Type of Cable : Twisted shielded pairs cable <30 m for input circuit
Range Compatibility : Modicon M221, Modicon M241, Modicon M251, Modicon M262
Ambient Air Temperature For Storage : -25-70 °C
Weight : 0.1 kg