Due to current global supply and market conditions, product prices may occasionally change. If there is any change in the price of items in your order, our customer support team will reach out to you for confirmation before proceeding further. We sincerely appreciate your understanding and thank you for your continued support.
Order Now & Get it by 2 - 3 Working Days
Sold by: Marketplace
Brand : Schneider Electric
Type : Logic Controller
Description
Schneider Electric TM221CE40T Logic Controller is part of the Modicon M221 Logic Controller range. It has 40 logical I/Os and is powered by 24 V DC. It is supplied with a removable screw terminal blocks for connecting the I/Os, a removable screw terminal block for connecting the power supply, a BR2032 coin-cell backup battery, and a cable for connecting the analog inputs.
M221 logic controllers have three types of built-in communication ports: Ethernet, RS 232/RS 485 serial connection, and USB Mini-B programming port. Allows control of simple machines. The capacity of the M221 logic controllers can be expanded with the Modicon TM3 expansion module offering.
Features
- It has 40 logical I/Os and is powered by 24 V DC.
- Includes removable screw terminal blocks for connecting the I/Os
| Brand | Schneider Electric |
| Item Name | Logic Controller |
| Model | TM221CE40T |
| Resistance To Electrostatic Discharge | 8 kV in air conforming to EN/IEC 61000-4-2, 4 kV on contact conforming to EN/IEC 61000-4-2 |
| Depth | 70 mm |
| Supply Voltage Limits | 20.4-28.8 V |
| Width | 160 mm |
| Discrete Output Current | 0.5 A |
| Supply | (serial 1)serial link supply: 5 V, <200 mA |
| Maximum Power Consumption in W | 17 W at 24 V (with max number of I/O expansion module), 4.9 W at 24 V (without I/O expansion module) |
| Data Backed Up | 256 kB built-in flash memory for backup of application and data |
| Data Storage Equipment | 2 GB SD card (optional) |
| Reset Time | 1 s automatic reset |
| Clock Drift | <= 30 s/month at 25-25 °C |
| Immunity To Microbreaks | 10 ms |
| Discrete Input Current | 7 mA for discrete input, 5 mA for fast input |
| Voltage State 1 Guaranteed | >= 15 V for input |
| Discrete Input Voltage | 24 V |
| Backup Time | 1 year at 25 °C (by interruption of power supply) |
| Voltage State 0 Guaranteed | <= 5 V for input |
| Discrete Input Number | 24 , discrete input 4 fast input conforming to IEC 61131-2 Type 1 |
| Resistance To Electromagnetic Fields | 10 V/m 80 MHz...1 GHz conforming to EN/IEC 61000-4-3, 3 V/m 1.4 GHz...2 GHz conforming to EN/IEC 61000-4-3, 1 V/m 2...2.7 GHz conforming to EN/IEC 61000-4-3 |
| Surge Withstand | 2 kV power lines (AC) common mode conforming to EN/IEC 61000-4-5, 2 kV relay output common mode conforming to EN/IEC 61000-4-5, 1 kV I/O common mode conforming to EN/IEC 61000-4-5, 1 kV shielded cable common mode conforming to EN/IEC 61000-4-5, 0.5 kV power lines (DC) differential mode conforming to EN/IEC 61000-4-5, 1 kV power lines (AC) differential mode conforming to EN/IEC 61000-4-5, 1 kV relay output differential mode conforming to EN/IEC 61000-4-5, 0.5 kV power lines (DC) common mode conforming to EN/IEC 61000-4-5 |
| Resistance To Fast Transients | 2 kV (power lines) conforming to EN/IEC 61000-4-4, 2 kV (relay output) conforming to EN/IEC 61000-4-4, 1 kV (I/O) conforming to EN/IEC 61000-4-4, 1 kV (Ethernet line) conforming to EN/IEC 61000-4-4, 1 kV (serial link) conforming to EN/IEC 61000-4-4 |
| Electromagnetic Emission | Conducted emissions - test level: 79 dBμV/m QP/66 dBμV/m AV ( power lines (AC)) at 0.15-0.5 MHz conforming to EN/IEC 55011, conducted emissions - test level: 73 dBμV/m QP/60 dBμV/m AV ( power lines (AC)) at 0.5-300 MHz conforming to EN/IEC 55011, conducted emissions - test level: 120...69 dBµV/m QP ( power lines) at 10-150 kHz conforming to EN/IEC 55011, conducted emissions - test level: 63 dBμV/m QP ( power lines) at 1.5-30 MHz conforming to EN/IEC 55011, radiated emissions - test level: 40 dBμV/m QP class A ( 10 m) at 30-230 MHz conforming to EN/IEC 55011, conducted emissions - test level: 79...63 dBμV/m QP ( power lines) at 150-1500 kHz conforming to EN/IEC 55011, radiated emissions - test level: 47 dBμV/m QP class A ( 10 m) at 200-1000 MHz conforming to EN/IEC 55011 |
| Analogue Input Resolution | 10 bits |
| Analogue Input Number | 2 at 0...10 V |
| Permitted Overload On Inputs | +/- 30 V DC for 5 min (maximum) for analog input, +/- 13 V DC (permanent) for analog input |
| Discrete Output Type | Transistor |
| LSB Value | 10 mV |
| Conversion Time | 1 ms per channel + 1 controller cycle time for analogue input analog input |
| Discrete Output Number | 16 transistor 2 fast output |
| Realtime Clock | With |
| Discrete Input Logic | Sink or source (positive/negative) |
| Discrete Input Voltage Type | DC |
| Maximum Number of I/O Expansion Module | 7 for Relay Output |
| Maximum Voltage Drop | <1 V |
| Maximum Tungsten Load | <12 W for output and fast output |
| Maximum Leakage Current | 0.1 mA for transistor output |
| Counting Input Number | 4 fast input (HSC mode) at 100 kHz 32 bits |
| Resistance To Conducted Disturbances | 10 V 0.15...80 MHz conforming to EN/IEC 61000-4-6, 3 V 0.1...80 MHz conforming to Marine specification (LR, ABS, DNV, GL), 10 V spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) conforming to Marine specification (LR, ABS, DNV, GL) |
| Maximum Cable Distance Between Devices | Shielded cable: <10 m for fast input, unshielded cable: <30 m for output, unshielded cable: <30 m for digital input, unshielded cable: <1 m for analog input, shielded cable: <3 m for fast output |
| Discrete Output Logic | Positive logic (source) |
| Positioning Functions | Position PTO 2 axe(s)pulse/direction mode (100 kHz), Position PTO 1 axe(s)CW/CCW mode (100 kHz) |
| Maximum Current Per Output Common | 4 A |
| Transmission Rate | 1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 15-15 m for RS485, 1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 3-3 m for RS232, 480 Mbit/s for USB |
| Discrete I/O Number | 40 |
| Configurable Filtering Time | 0 ms for input, 3 ms for input, 12 ms for input |
| Discrete Output Voltage | 24 V DC |
| Memory Capacity | 256 kB for user application and data RAM with 10000 instructions, 256 kB for internal variables RAM |
| Execution Time For 1 KInstruction | 0.3 ms for event and periodic task |
| Absolute Accuracy Error | +/- 1 % of full scale for analog input |
| Resistance To Magnetic Fields | 30 A/m 50/60 Hz conforming to EN/IEC 61000-4-8 |
| Regulation Loop | Adjustable PID regulator up to 14 simultaneous loops |
| Exct Time For Event Task | 60 µs response time |
| Execution Time Per Instruction | 0.2 µs Boolean |
| Maximum Size of Object Areas | 512 %KW constant words, 255 %TM timers, 255 %C counters, 8000 %MW memory words, 512 %M memory bits |
| Vibration Resistance | 3.5 mm at 5-8.4 Hz on symmetrical rail, 3.5 mm at 5-8.4 Hz on panel mounting, 1 gn at 8.4-150 Hz on symmetrical rail, 1 gn at 8.4-150 Hz on panel mounting |
| Ambient Air Temperature For Operation | -10-55 °C (horizontal installation), -10-35 °C (vertical installation) |
| Standards | EN/IEC 60664-1, EN/IEC 61131-2, EN/IEC 61010-2-201 |
| Communication Port Protocol | USB port: USB - SoMachine-Network, non isolated serial link: Modbus master/slave - RTU/ASCII or SoMachine-Network, Ethernet |
| Control Signal Type | A/B, pulse/direction, single phase |
| Storage Altitude | 0-3000 m |
| Ambient Air Temperature For Storage | -25-70 °C |