Brand : Schneider Electric
Item Name : Illuminated Selector Switch
Model : XB5AK125M5
Resistance to Electrostatic Discharge : 6 kV on contact (on metal parts) conforming to IEC 61000-4-2, 8 kV in free air (in insulating parts) conforming to IEC 61000-4-2
Conventional Free Air Thermal Current : 10 A conforming to EN/IEC 60947-5-1
Rated Insulation Voltage : 600 V (pollution degree 3) conforming to EN 60947-1
Rated Impulse Withstand Voltage : 6 kV conforming to EN 60947-1
Rated Supply Voltage : 230...240 V AC at 50/60 Hz
Bezel Material : Dark Grey Plastic
Bulb Base : Integral LED
Cap/Operator Or Lens Color : Orange
Compatibility Code : XB5
Connections - Terminals : Screw clamp terminals, <= 2 x 1.5 mm² with cable end conforming to EN/IEC 60947-1, screw clamp terminals, >= 1 x 0.22 mm² without cable end conforming to EN/IEC 60947-1
Contact Operation : Slow-break
Contacts Material : Silver alloy (Ag/Ni)
Current Consumption : 14 mA
Depth : 70 mm
Electrical Reliability : λ < 10exp(-6) at 5 V and 1 mA in clean environment conforming to EN/IEC 60947-5-4, λ < 10exp(-8) at 17 V and 5 mA in clean environment conforming to EN/IEC 60947-5-4
Height : 42 mm
IK Degree Of Protection : IK06 conforming to IEC 50102
IP Degree Of Protection : IP66 conforming to IEC 60529, IP67 conforming to IEC 60529, IP69, IP69K
Light Source : Universal LED
Mechanical Durability : 1000000 cycles
Mounting Diameter : 22 mm
Operator Position Information : 2 positions 90°
Operator Profile : Orange standard handle
Positive Opening : With conforming to EN/IEC 60947-5-1 appendix K
Protective Treatment : TH
Certifications : LROS (Lloyds register of shipping), DNV, GL, CSA, UL, BV
Range Of Product : Harmony XB5
Sale Per Indivisible Quantity : 1
Service Life : 100000 h at rated voltage and 25 °C
Shape Of Screw Head : Cross compatible with Philips no 1 screwdriver, cross compatible with pozidriv No 1 screwdriver, slotted compatible with flat Ø 4 mm screwdriver, slotted compatible with flat Ø 5.5 mm screwdriver
Shape of Signaling Unit Head : Round
Shock Resistance : 30 gn (duration = 18 ms) for half sine wave acceleration conforming to IEC 60068-2-27, 50 gn (duration = 11 ms) for half sine wave acceleration conforming to IEC 60068-2-27
Signalling Type : Steady
Short-Circuit Protection : 10 A cartridge fuse type gG conforming to EN/IEC 60947-5-1
Tightening Torque : 0.8-1.2 N.m conforming to EN 60947-1
Supply Voltage Limits : 195-264 V AC
Terminals Description ISO n°1 : (11-12)NC, (13-14)NO
Type Of Operator : Stay put
Width : 30 mm
Contacts Type And Composition : 1 NO + 1 NC
NEMA Degree Of Protection : NEMA 13, NEMA 4X
Customizable : No
Head Type : Standard
Resistance To Electromagnetic Fields : 10 V/m conforming to IEC 61000-4-3
Resistance To High Pressure Washer : 7000000 Pa at 55 °C, distance : 0.1 m
Contacts Usage : Standard contacts
Surge Withstand : 1 kV conforming to IEC 61000-4-5
Resistance to Fast Transients : 2 kV conforming to IEC 61000-4-4
Electromagnetic Emission : Class B conforming to IEC 55011
Operating Torque : 0.14 N.m NO changing electrical state
Vibration Resistance : 5 gn (f= 2-500 Hz) conforming to IEC 60068-2-6
Ambient Air Temperature For Operation : -40-70 °C
Ambient Air Temperature For Storage : -40-70 °C
Standards : EN/IEC 60947-5-4, CSA C22.2 No 14, JIS C8201-5-1, EN/IEC 60947-5-1, EN/IEC 60947-1, UL 508, JIS C8201-1
Rated Operational Current : 3 A at 240 V, AC-15, A600 conforming to EN/IEC 60947-5-1, 6 A at 120 V, AC-15, A600 conforming to EN/IEC 60947-5-1, 0.1 A at 600 V, DC-13, Q600 conforming to EN/IEC 60947-5-1, 0.27 A at 250 V, DC-13, Q600 conforming to EN/IEC 60947-5-1, 0.55 A at 125 V, DC-13, Q600 conforming to EN/IEC 60947-5-1, 1.2 A at 600 V, AC-15, A600 conforming to EN/IEC 60947-5-1
Electrical Durability : 1000000 cycles, AC-15, 2 A at 230 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C, 1000000 cycles, AC-15, 3 A at 120 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C, 1000000 cycles, AC-15, 4 A at 24 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C, 1000000 cycles, DC-13, 0.2 A at 110 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C, 1000000 cycles, DC-13, 0.5 A at 24 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C
Device Presentation : Complete Product
Electrical Shock Protection Class : Class II conforming to IEC 60536
Weight : 0.516 kg